Summary |
General Operation |
Suitable for |
Ref.Number |
Sensor Validation |
Produces a (4 to 20) mA output proportional to average of two sensor inputs as long as both sensors are in bounds. If either sensor goes out of bounds it is rejected and the output then becomes proportional to the good sensor. A relay contact is set to annunciate the sensor failure which can be changed at the next scheduled maintenance. |
MED2213 |
02011111
Download |
General pulse totaliser |
PV is taken as a flow rate. Output 2, relay A is pulsed for a user-configurable time when the integrated total reaches a user-configurable value. |
MED2113, MED2122, MED2133 |
02011011
Download |
Rate of change limiter |
Operates as a standard transmitters but limits the maximum rate of change of the output to a user defined value. |
MED2113 |
02010921
Download |
Peak/Valley Pick & Hold |
Provides a display an analogue O/P proportional to either the peak or valley input which is reset by an external digital. The peak/valley also decays as a rate defined in TFML3 |
MED2213 |
02010911
Download |
Pulse Totaliser |
Takes (0 to 10) V DC input equivalent to (0 to 400) m3 hr and provide 2 outputs. Output 1 (4 to 20) mA = (0 to 400) m3 hr, output 2 relay 1 high alarm, relay 2 pulse per total. For pulse output, relay on time = 100 ms |
MED2113 |
02010211
Download |
PI control Relay Output |
This is the conventional PI control whereby a control signal is derived which is proportional to the error and the integral of the error. The output is sent to the proportioning relay output
The setpoint, P&I constants and the relay cycle time are entered via TFNL registers.
Anti-windup is included i.e the integral is reset to Zero whenever the error is outside the proportional band |
MED2133 |
02010711
Download |
PID - 3 term control - continuous |
This is the conventional PID control whereby a control signal is derived which is proportional to the error, the integral of the error and the derivative of the error. The setpoint and PID constants are entered via TFnL registers.
Anti-windup is included i.e the integral is reset to Zero whenever the error is outside the proportional band |
MED2113 |
02010311
Download |
A-B |
Provides an analogue output proportional to the difference between the two inputs. |
MED2211 |
01120412
Download |
A+B
or Average |
Provides an output equal to the sum or average of both inputs (or some other sub-multiple of the sum).
Both inputs are summed together and divided by TFML1, The output is then scaled according to TFML2 and TFML3 and sent to the (4 to 200 mA output. |
MED2211, MED2213 |
01120421
Download |
Sample and Hold |
(4 to 20) mA output related to input, the digital input initiates the hold, and the digital output is used as an alarm. |
MED2113 |
01120611
Download |
High Input Selector |
This module takes two inputs and produces a (4 to 20) mA output proportional to the highest of the two inputs.
Sensor A and B are set up in the normal way. The difference between the highest is selected and output from Channel 1 as an analogue signal, (4 to 20) mA ranges from TFNL1 to TFNL2.
Channel 2 output remains operational on channel 2 input as standard. |
MED2213, MED2211 |
01120512
Download |
Divider |
The TFML takes 2 inputs; A & B. Output 1 is proportional to A/B (default) or A*B. Output 2 remains under normal operation, unaffected by TFML |
MED2211, MED2213, MED2411, MED2413 |
03011011
Download |